Here, TOA's Data Library equipped with a search engine offers its CAD drawings made out in pdf and dwg forms, EASE data, specification sheets, brochures, instruction and installation manuals, and a wealth of other product data for your downloading.

SX-2100AO Audio Output Unit

SX-2100AO

The SX-2100AO is an audio output of the matrix system and can be mounted in an EIA equipment rack (2 U size). Multiple units can be decentralized in a whole system. It is equipped with eight audio outputs, and two inputs can be mixed and output. It is also equipped with eight control inputs, and eight control outputs. The SX-2100AO receives audio signals from the audio input unit via digital transmission, but an analog audio input function (1 channel) enables simultaneous all-zone calls for use in emergency situations. Audio output levels are indicated on the level meters provided for each output channel. Volumes can be adjusted for each channel using the volume controls on the front panel or the SX-2000 software. The volume controls can be locked. Any output channel can be monitored using the internal speaker. Two channels of local audio inputs with control inputs are provided as the dedicated audio inputs. Its functions include an amplifier switching function that automatically switches the power amplifier to the standby amplifier if the power amplifier fails, and a surveillance function that self-diagnoses the speaker lines. Equipped with two channels of interfaces for connecting to the Emergency Power Supply units, making it possible to configure the system to operate during a power failure. One control IN/OUT interface allows the number of control inputs and outputs to be increased. The SX-2100AO has two power inputs and can support a dual-redundant power supply system.

Specification
* 0 dB = 1 V
Power Source Usable power supply unit: VX-200PS
24 V DC (operational range: 20 V - 40 V DC)
Two power inputs construction enables dual-redundant power supply.
Current Consumption 1.7 A or less (maximum value in the power operating range)
1.2 A or less (when operated on 24 V DC)
Note: But except current consumption of the external equipment of which power is supplied
from the unit.
Indication 18 alphanumeric characters, Level indication (8 outputs, monitor), Status indicators,
Power indicator, Standby indicator, CPU OFF indicator
Operation Function button, Output level control, Monitor speaker volume control, ON/OFF switch,
Operation button
PA Link
Audio Output 8 outputs and standby AMP, 0 dB*, suitable load: 600 Ω or above, electronically-balanced,
RJ45 Connector
monitoring possible using built-in speaker
Audio Output Characteristic Frequency response: 20 Hz - 20 kHz
Sampling frequency: 48 kHz
D/A converter: 24 bit
Connection Cable Shielded Category 5 twisted pair cable (CAT5-STP)
Maximum Cable Distance 5 m (16.4 ft)
Usable Amplifier VP-2064, VP-2122, VP-2241 or VP-2421 (VP-200VX is required for each amplifier.)
Local Audio Input
Audio Input 2 inputs, 0 dB*, 10 kΩ, electronically-balanced, RJ45 Connector
Audio Input Characteristic Frequency response: 20 Hz - 20 kHz
Sampling frequency: 48 kHz
A/D converter: 24 bit
Control Input 2 inputs, no-voltage make contact input, open voltage: 12 V DC,
short-circuit current: 2 mA, photo coupler input
Connection Cable Shielded Category 5 twisted pair cable (CAT5-STP)
SX Link
Network I/F 2 100BASE-TX circuits, RJ45 connector, decentralized installation possible
Connection Cable/Device Shielded Category 5 twisted pair cable (CAT5-STP)
To be connected via the switching hub specified by TOA
Note: This network must be made completely independent from other LAN.
Maximum Cable Distance 100 m (109.36 yd) (between this unit and a switching hub)
Analog Link
Input/Output Connector Input: 1 input, RJ45 connector
Output: 1 output, RJ45 connector
Connection Cable Shielded Category 5 twisted pair cable (CAT5-STP)
(1 pair of audio wire + 1 pair of CPU OFF + 1 pair of control wire (system reset/standby)
+ 1 pair of connection check wire)
Maximum Cable Distance Total length of analog link: 800 m (874.89 yd)
DS Link
Usable Unit VX-2000DS
Connector/Cable 2 interface, RJ45 Connector, Shielded Category 5 twisted pair cable (CAT5-STP)
Maximum Cable Distance 5 m (16.4 ft)
CI/CO Link
Usable Unit SX-2000CI or SX-2000CO
Connector/Cable 1 interface, RJ45 Connector,
Shielded Category 5 twisted pair cable (CAT5-STP)
Maximum Cable Distance 800 m (874.89 yd)
Speaker Line Failure Detection Section
Connector/Cable Removable terminal block, SP/AMP: 8 pins, STANDBY AMP: 2 pins,
AWG 24 - AWG 16
Maximum Input 100 Vrms, 5 Arms
Fault Detection System Short circuit, open circuit, ground fault
Method Impedance or End of line
End of Line In case of normal: Terminated by 470 kΩ between the speaker line and the shield
In case of open: Opened between the speaker line and the shield
Impedance Minimum load: 2 kΩ (5 W) at 100 V line
Control Input 8 inputs, no-voltage make contact input, open voltage: 40 V DC or less,
short-circuit current: 2 mA, photo coupler input, removable terminal block (6 pins)
Control Output 8 outputs, C contact, no-voltage make contact output, relay contact output
(withstand voltage: 40 V DC, control current: 2 - 300 mA),
removable terminal block (6 pins)
Operating Temperature 0 ℃ to +40 ℃ (32 ゜F to 104 ゜F)
Operating Humidity 35 % to 80 %RH (no condensation)
Finish Panel: Aluminum, black, alumite
Case: Surface-treated steel plate
Dimensions 482 (W) × 88.4 (H) × 349 (D) mm (18.98 × 3.48" × 13.74")"
Weight 7.1 kg (15.65 lb)
Accessory Removable terminal plug (8 pins) …4, Removable terminal plug (6 pins) …8,
Removable terminal plug (4 pins) …1, Removable terminal plug (2 pins) …1,
Rack mounting screw …4